Functionality; Function Block; Signals - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 15
Monitoring
15.4.2
15.4.3
15.4.4
540

Functionality

The circuit breaker condition monitoring function (SSCBR) is used to monitor
different parameters of the breaker condition. The breaker requires maintenance
when the number of operations reaches a predefined value. For a proper
functioning of the circuit breaker, it is essential to monitor the circuit breaker
operation, spring charge indication or breaker wear, travel time, number of
operation cycles and estimate the accumulated energy during arcing periods.

Function block

SSCBR
I3P*
OPENPOS
BLOCK
CLOSEPOS
BLKALM
INVDPOS
TRIND
TRCMD
POSOPEN
TRVTOPAL
POSCLOSE
TRVTCLAL
PRESALM
OPERALM
PRESLO
OPERLO
SPRCHRST
CBLIFEAL
SPRCHRD
MONALM
RSTCBWR
IPOWALPH
RSTTRVT
IPOWLOPH
RSTIPOW
SPCHALM
RSTSPCHT
GPRESALM
GPRESLO
IEC13000231-2-en.vsd
IEC13000231 V2 EN-US
Figure 267:
SSCBR function block

Signals

Table 387:
SSCBR Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKALM
BOOLEAN
TRIND
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
PRESALM
BOOLEAN
PRESLO
BOOLEAN
SPRCHRST
BOOLEAN
SPRCHRD
BOOLEAN
RSTCBWR
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for current input
0
Block all the alarm and lockout indication
0
Block all the alarms
0
Trip command from trip circuit
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Pressure alarm indication from CB
0
Pressure lockout indication from CB
0
CB spring charging started indication signal
0
CB spring charged indication signal
0
Reset of CB remaining life and operation counter
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v11
GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11
PID-3267-INPUTSIGNALS v10
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents