Station communication
18.4.13.5
Table 484:
GOOSEXLNRCV Non group settings (basic)
Name
Operation
18.4.13.6
18.5
18.5.1
18.5.2
666

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The xxx_VALID outputs will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
At least one of the inputs of this GOOSE block must be linked
either in SMT by means of a cross or in ACT by means of a
GOOSE connection (if easy GOOSE engineering is enabled) to
receive any data. Only those outputs whose source input is linked/
connected will be updated.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the xxx_VALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the xxx_VALID output will be LOW.

IEC/UCA 61850-9-2LE communication protocol

Introduction

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED
to communicate with devices providing measured values in digital format,
commonly known as Merging Units (MU). The rear access points are used for the
communication.

Function block

The function blocks are not represented in the configuration tool.
The signals appear only in the SMT tool when merging units (MU)
Step
Default
-
Off
1MRK 505 394-UEN A
Description
Operation Off/On
GUID-903B5E3F-DC92-4D0A-B4D5-59DD01F36458 v1
GUID-6814F62B-8D99-4679-A11E-68048D1AC424 v2
GUID-FE2AC08A-2E04-4E73-8CA4-905522B1026A v2
GUID-2581F3AD-7487-4C80-BDF3-9C6EC9F2E43C v3
Line differential protection RED650 2.2 IEC