Section 14
Logic
14.14.3
14.14.4
486
BLOCK
RESET
IN
999 999 s
tWarning
tAlarm
-1
q
= unit delay
IEC13000290 V2 EN-US
Figure 246:
TEIGAPC logics
The main features of TEIGAPC
•
Applicable to long time integration up to 999 999.9 seconds
•
Supervision of overflow
•
Possibility to define a warning and an alarm with the resolution of 10
milliseconds
•
Retain the integration value
•
Possibilities for blocking and reset of the total integrated time
•
Report of the integrated time
Function block
TEIGAPC
BLOCK
WARNING
IN
ALARM
RESET
OVERFLOW
ACCTIME
IEC14000014-1-en.vsd
IEC14000014 V1 EN-US
Figure 247:
TEIGAPC function block
Signals
Table 327:
TEIGAPC Input signals
Name
Type
BLOCK
BOOLEAN
IN
BOOLEAN
RESET
BOOLEAN
Time Integration
with Retain
-1
q
a
a>b
b
a
a>b
b
a
a>b
b
Default
Description
0
Freeze the integration and block the other outputs
0
The input signal that is used to measure the
elapsed time, when its value is high
0
Reset the integration time
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
ACCTIME
OVERFLOW
AND
WARNING
AND
ALARM
AND
IEC13000290-2-en.vsd
GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2
PID-6836-INPUTSIGNALS v2
Technical manual