1MRK 505 394-UEN A
21.4
21.4.1
21.4.2
Table 593:
TERMINALID Non group settings (basic)
Name
Values (Range)
StationName
StationNumber
ObjectName
ObjectNumber
UnitName
UnitNumber
IEDMainFunType
TechnicalKey
Line differential protection RED650 2.2 IEC
Technical manual
If the IED is restarted while set to IED TESTMODE by a binary
input all functions will be temporarily unblocked during startup,
which might cause unwanted operations.
The TESTMODE function block might be used to automatically block functions
when a test handle is inserted in a test switch. A contact in the test switch (RTXP24
contact 29-30) can supply a binary input which in turn is configured to the
TESTMODE function block.
Each of the functions includes the blocking from the TESTMODE function block.
The functions can also be blocked from sending events over IEC 61850 station bus
to prevent filling station and SCADA databases with test events, for example
during a commissioning or maintenance test.

IED identifiers TERMINALID

Functionality

IED identifiers (TERMINALID) function allows the user to identify the individual
IED in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit
names.

Settings

Unit
0 - 18
-
0 - 99999
-
0 - 18
-
0 - 99999
-
0 - 18
-
0 - 99999
-
0 - 255
-
0 - 16
-
0 - 16
-
0 - 16
-
0 - 16
-
Step
Default
1
Station name
1
0
1
Object name
1
0
1
Unit name
1
0
1
0
1
AA0B0Q0A0
1
1
1
Section 21
Basic IED functions
GUID-3C49A222-FFE4-492B-A96C-9E9965FA2CB4 v2
Description
Station name
Station number
Object name
Object number
Unit name
Unit number
IED main function type for
IEC60870-5-103
Technical key (part 1)
Technical key (part 2)
Technical key (part 3)
Technical key (part 4)
IP15060-1 v2
M15324-3 v6
PID-6801-SETTINGS v1
793