Parameter Table

This parameter table shows the most important parameters.
Default settings are bold type. Refer to the Technical
Manual for a complete list of parameters.
No.
(Addr.
Name
Hex)
A1: Initialization
0: English
A1-00
Language
1: Japanese
(100H)
Selection
7: Chinese
0: View and set A1-01 and A1-04.
U -
1: User Parameters (access to a set of
A1-01
Access Level
parameters selected by the user, A2-01 to
(101H)
Selection
A2-32)
2: Advanced Access (access to view and
set all parameters)
0: No initialization
1110: User Initialize (parameter values
A1-03
Initialize
must be stored using parameter o2-03)
(103H)
Parameters
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: oPE04 error reset
A1-04
When the value set into A1-04 does not
Password
(104H)
match the value set into A1-05, parameters
A1-01 through A1-03, A1-06, and A2-01
A1-05
Password
through A2-33 cannot be changed.
(105H)
Setting
A2: User Parameters
A2-01 to
Recently edited parameters are listed here.
A2-32
User Parameters
The user can also select parameters to
(106H to
1 to 32
appear here for quicker access.
125H)
0: Parameters A2-01 to A2-32 are
reserved for the user to create a list of
User Parameter
User Parameters.
A2-33
Automatic
1: Save history of recently viewed
(126H)
Selection
parameters. Recently edited parameters
will be saved to A2-17 through A2-32 for
quicker access.
b1: Operation Mode Selection
0: Digital operator
b1-02
Run Command
1: Digital input terminals
(181H)
Selection 1
2: MEMOBUS/Modbus communications
3: Option PCB
0: Input status is read once and processed
immediately (for quicker response)
b1-06
Digital Input
1: Input is read twice and processed
(185H)
Reading
only if the status is the same in both
readings (robust against noisy signals)
0: Run command is not accepted while
Run Command
in Programming Mode.
b1-08
Selection in
1: Run command is accepted while in
(187H)
Programming
Programming Mode.
Mode
2: Prohibit entering Programming Mode
during run.
0: Disregarded. A new Run Command
must be issued.
b1-17
Run Command
1: Allowed. Converter will start
(1C6H)
at Power Up
immediately if Run Command is present at
power up.
YASKAWA ELECTRIC TOEP C710656 06A YASKAWA Power Regenerative Converter - D1000 Quick Start Guide
Description
parameters can also be viewed.
No.
(Addr.
Name
Hex)
0: Digital operator
1: Control circuit terminal (analog input)
Voltage
b1-18
2: MEMOBUS/Modbus communications
Reference
(179H)
3: Option card
Source
7: Input voltage based control 1
8: Input voltage based control 2
b4: Timer Function
Sets the on-delay times for a digital timer
b4-01
Timer Function
output (H2-
(1A3H)
On-Delay Time
The output is triggered by a digital input
programmed to H1-
Sets the off-delay times for a digital timer
b4-02
Timer Function
output (H2-
(1A4H)
Off-Delay Time
The output is triggered by a digital input
programmed to H1-
C1: Voltage Increase and Decrease Times
Sets the output voltage increase time in
seconds.
C1-20
Voltage Increase
Set the time to increase from 0% to 100%.
(265H)
Time
400 V Class: 800 V/C1-20 (V/s)
200 V Class: 400 V/C1-20 (V/s)
Sets the output voltage decrease time in
seconds.
C1-21
Voltage
Set the time to decrease from 100% to 0%.
(266H)
Decrease Time
400 V Class: 800 V/C1-21 (V/s)
200 V Class: 400 V/C1-21 (V/s)
C6: Carrier Frequency
There is normally no need to change this
parameter from the default value.
If you change this setting carelessly, the
Carrier
C6-02
converter may be damaged.
Frequency
(224H)
1: 2 kHz
Selection
2: 4 kHz
3: 6 kHz
F: User-defined
There is normally no need to change this
parameter from the default value.
Carrier
C6-03
Set the carrier frequency that is specified
Frequency
(225H)
by the manufacturer.
Upper Limit
If you change this setting carelessly, the
converter may be damaged.
C7: DC Bus Voltage Control
DC Bus Voltage
C7-01
Control (Avr)
Sets the proportional gain for DC bus
(253H)
Proportional
voltage control (Avr).
Gain
DC Bus Voltage
C7-02
Sets the integral time for DC bus voltage
Control (Avr)
(254H)
control (Avr).
Integral Time
DC Bus Voltage
C7-03
Control (Avr)
Sets the primary delay time constant for
(255H)
Primary Delay
DC bus voltage control (Avr).
Time Constant
Reactive Current
Reference Bias
0: Disabled
C7-12
Automatic
1: Enabled (Automatically calculate the
(26EH)
Calculation
reactive current reference bias.)
Selection
8 Parameter Table
Description
=12).
=18.
=12).
=18.
<1>
<1>
35