Factory Default Setting; Setting With Dip Switch - Omron F3SG series User Manual

Safety light curtain
Hide thumbs Also See for F3SG series:
Table of Contents

Advertisement

System Operation and Functions
• Pre-Reset mode
Pre Reset SW
Unblocked
Beam state
Reset SW
OSSD
Auxiliary Output *
INT-LK Indicator
* When Auxiliary Output is set to Pre-Reset Enabled by the Configuration Tool.

2-9-2. Factory Default Setting

The factory default setting is Auto Reset mode enabled, Start Interlock, Restart Interlock and Pre-
Reset mode disabled.

2-9-3. Setting with DIP Switch

The user can select the mode from Auto Reset, Manual Reset or Pre-Reset by the DIP Switch.
When configured to Manual Reset mode, the Start Interlock and Restart Interlock are enabled.
When configured to Pre-Reset mode, the function is activated with the following conditions:
• Maximum number of times the F3SG-RA is blocked after input of PRE-RESET signal: Infinite (The
F3SG-RA must be blocked at least once.)
• Maximum period of time from input of PRE-RESET signal to input of RESET signal: 8 s
Make sure the Position 8 of the DIP Switch is set to DIP Switch Enabled to activate the settings by the DIP Switch.
Refer to Chapter 3 Setting with DIP Switch for more information on setting this function by the DIP Switch.
F3SG-R
36
User's Manual
ON
OFF
Blocked
ON
OFF
ON
OFF
ON
OFF
ON
OFF
T1
T3
T2
T1: Push time: must be T1 >= 300 ms
T2: Pre-reset limit time between Pre-reset and Reset:
must be T2 <= 8 s (Factory default setting)
T3: Push time: must be T3 >= 300 ms
T1
T3
T2
Flash
Flash
once
twice
Solid
on