Standard Muting Mode With Four Muting Sensors Using Pnp Outputs - Omron F3SG series User Manual

Safety light curtain
Hide thumbs Also See for F3SG series:
Table of Contents

Advertisement

Input/Output Circuit and Applications
5-2-7. Standard Muting Mode with four Muting Sensors using
PNP Outputs
The following is the example of External Device Monitoring disabled, Auto Reset mode, PNP output
and External Test in 24 V Active.
[DIP Switch settings] *5
Receiver
Emitter
Configure functions with the DIP Switches before wiring.
[Wiring Example]
Reflector
Muting
Sensor
A1
(PNP
output)
*1. Also used as Override input line.
*2. Make sure to connect an override cancel switch to the Reset line
when using the override function. Otherwise the override state may
not be released by the override cancel switch, resulting in serious
injury.
*3.Refer to 5-4. Connectable Safety Control Units for more information.
*4.The safety controller and the F3SG-R must share the power supply
or be connected to the common terminal of the power supply.
*5. The functions are configurable with DIP Switch. Refer to Chapter 3
Setting with DIP Switch for more information on setting the functions
by the DIP Switch.
F3SG-R
190
User's Manual
Function
EDM Disabled (factory default setting)
Auto Reset (factory default setting)
PNP (factory default setting)
External Test: 24 V Active (factory default setting)
F39-JG A-L
S1
B2
B1
A2
DIP-SW1
F39-JG A-D
ML
S2
*2
IN1
Controller *3 *4
+24 VDC
Power Supply
0 VDC
S1: Test Switch (Connect the line to 0 V if this
switch is not required)
S2: Lockout/Interlock Reset Switch,
Override Switch or Override Cancel Switch
ML: Muting lamp
A1, A2, B1, B2: Muting sensor
Unblocked
Beam state
Blocked
Test Switch (S1)
MUTE A
MUTE B
OSSD
DIP-SW2
: Indicates a switch position.
IN2
Safety