Input/Output Circuit and Applications

5-2-11. Pre-Resest Mode using PNP Output

The following is the example of External Device Monitoring disabled, Pre-Reset mode, PNP output and
External Test in 24 V Active.
[DIP Switch settings] *4
Receiver
Emitter
Configure functions with the DIP Switches before wiring.
[Wiring Example]
S1: Test Switch (Connect the line to 0 V if this switch is
S2: Lockout/Interlock Reset Switch
S3: Pre-Reset Switch
PLC: Programmable controller
*1. Refer to 5-4. Connectable Safety Control Units for
*2. The safety controller and the F3SG-R must share the
*3. When connecting to the PLC, the output mode must
*4. The functions are configurable with DIP Switch. Refer
F3SG-R
194
User's Manual
Function
EDM Disabled (factory default setting)
Pre-Reset
PNP (factory default setting)
External Test: 24 V Active (factory default setting)
F39-JG A-L
S1
not required)
(Used for monitoring only. NOT related to safety system.)
more information.
power supply or be connected to the common terminal
of the power supply.
be changed with the Configuration Tool.
to Chapter 3 Setting with DIP Switch for more
information on setting the functions by the DIP Switch.
Pre-Reset Switch (S3)
Unblocked
Beam state
Blocked
Reset Switch (S2)
OSSD
T1: Push time: must be T1 >= 300ms
T2: Pre-reset limit time between Pre-reset and Reset: must be T2 <= 60s
T3: Push time: must be T3 >= 300ms
DIP-SW1
F39-JG A-D
S2
S3
IN
PLC *3
T1
T3
T2
DIP-SW2
: Indicates a switch position.
+24 VDC
Power Supply
0 VDC
IN1
IN2
Safety
Controller *1 *2