Setting with DIP Switch
Teach-in setting is valid
LED Indicator
CFG
(5) Restart
Press and hold the reset switch (for 1 s or longer) or power cycle the F3SG-RA to enable and activate
the setting. Check if the Fixed Blanking zone is properly configured.
 Others
• When the teach-in is performed with the all Fixed Blanking zone being unblocked, the Fixed Blanking
is configured as Disabled. Teach-in is available under cascade connection as well. In such a case,
use the primary sensor's Push Switch to perform teach-in with the similar steps.
• When the F3SG-RA is in the cascade connection, the teach-in setting is performed for each channel
independently. This allows different F3SG-RA's to have different teach-in settings depending on the
position or size of the blocking object. For example, when the F3SG-RA at Channel 1 is blocked, that
F3SG-RA only has the Fixed Blanking setting.
Upper
11th beam
10th beam
5th beam
4th beam
Lower
Upper
13th beam
12th beam
7th beam
6th beam
Lower
• The teach-in result for Fixed Blanking and Floating Blanking cannot be saved together. When the
Teach-in is ferformed for Floating Blanking, the result of the teach-in for Fixed Blanking is cleared.
F3SG-R
114
User's Manual
Teach-in setting is invalid
Status
LED Indicator
CFG
Blink
Upper
Fixed Blanking zone
Fixed Blanking zone:
4th to 11th beams
Allowable beam:
2 lower beams/2 upper beams
Lower
4th & 5th beams
10th & 11th beams
Upper
Fixed Blanking zone
Fixed Blanking zone:
6th to 13th beams
Allowable beam:
2 lower beams/2 upper beams
Lower
6th & 7th beams
12th & 13th beams
Status
Blink
Upper
Upper
11th beam
10th beam
5th beam
4th beam
Lower
Lower
Upper
Upper
Lower
Lower
Fixed Blanking zone
Fixed Blanking zone:
4th to 11th beams
Allowable beam:
2 lower beams/2 upper beams
4th & 5th beams
10th & 11th beams
Fixed Blanking: Disabled