5.
The workpiece passed F3SG-RA's detection zone
A1 : Muting sensor to be connected
to muting input A
B1 : Muting sensor to be connected
to muting input B
A workpiece has passed F3SG-RA's detection zone. When the muting end wait time: T4 (1 s:
configurable) passes after the F3SG-RA is unblocked, the muting state is released.
 Installation Distance
Distances between muting sensors A1, B1, and F3SG-RA must be configured based on speed of a
workpiece.
Distance d1 between muting sensors A1 and B1 must satisfy Equations (1) and (2).
Distance d2 between muting sensor A1 and F3SG-RA must satisfy Equations (3) and (4).
Time t1 [ s ] to turn muting sensors A1 and B1 in this order is:
t1 = d1 / V . . . . . . . . . . . Equation (1)
Time t1 in Equation (1) for F3SG-RA to enter muting state is within a range shown below:
T1min < t1 < T1max. . . . Equation (2)
The values of T1
min
Time t2 [ s ] for a workpiece to pass F3SG-RA's detection zone after passing the muting sensor A1 is:
t2 = d2 / V . . . . . . . . . . . . Equation (3)
Time t2 in Equation (3) must satisfy following condition:
t2 < T5 . . . . . . . . . . . . . . Equation (4)
The value of T5 can be changed by the Configuration Tool.
Sensors must be installed so that person's passing should not cause muting state.
Hazardous zone
A1 B1
d1
d2
d1 [ m ] : Distance between muting sensors A1 and B1
V [ m/s ] : Approach speed of a workpiece
T1min [ s ] : Muting input time limit value (minimum)
T1max [ s ] : Muting input time limit value (maximum)
and T1
can be changed by the Configuration Tool.
max
d2 [ m ] : Distance between muting sensor A1 and F3SG-RA
V [ m/s ] : Approach speed of a workpiece
T5: Exit-only muting delay time
System Operation and Functions
F3SG-RA
Workpiece
V
E
F3SG-R
61
User's Manual