5-2-10. Exit-Only Muting Mode with F3W-MA (L-Shaped

Configuration with 4-Joint Plug/Socket Connector)

The following is the example of F3SG-RA with Scan Code A, External Device Monitoring disabled,
Auto Reset mode, PNP output and External Test in 24 V Active, and F3W-MA with Scan Code B,
Chattering and Void Space Prevention 1, Off-Delay 100 ms and Muting Enable enabled.
[DIP Switch settings]*1
Receiver
F3SG-RA
Emitter
Receiver
F3W-MA
Emitter
Configure functions with the DIP Switches before wiring.
[Wiring Example]
F3W-MA Emitter
(Primary)
F39-GCN4-L
F39-JG
A-L
S1: Test Switch (Connect the line to 0 V if this switch is not required)
S2: Lockout/Interlock Reset Switch, Override Switch or Override Cancel Switch
S3: Muting Enable Switch
ML: Muting lamp
*1. The functions are configurable with DIP Switch. For the DIP Switch of the F3SG-RA, refer to the Chapter 3 Setting with DIP
Switch. For the DIP Switch of the F3W-MA, refer to the Smart Muting Actuator F3W-MA Series User's Manual.
*2. DIP Switch Bank 2 of F3W-MA receiver is not used.
*3. Also used as Override input line.
*4. Make sure to connect an override cancel switch to the Reset line when using the override function. Otherwise the override
state may not be released by the override cancel switch, resulting in serious injury.
*5. Refer to 5-4. Connectable Safety Control Units for more information.
*6. The safety controller and the F3SG-R must share the power supply or be connected to the common terminal of the power
supply.
Function
Scan Code A (factory default setting)
EDM Disabled (factory default setting)
Auto Reset (factory default setting)
PNP (factory default setting)
Scan Code A (factory default setting)
External Test: 24 V Active (factory default setting)
Scan Code B (factory default setting)
Chattering and Void Space Prevention 1
Off-Delay 100 ms
Muting Enable Enabled
Scan Code B (factory default setting)
F3W-MA Receiver
(Primary)
F39-GCN4-D
S2
*4
S1
Input/Output Circuit and Applications
DIP-SW1
F39-JG
A-D
S3
ML
IN1
IN2
Safety
Controller *5 *6
DIP-SW2
-
-
*2
*2
*2
*2
*2
*2
-
: Indicates a switch position.
+24 VDC
Power Supply
0 VDC
F3SG-R
User's Manual
E
193