Setting With Rotary Switch/End Cap - Omron F3SG-*RR Series Quick Installation Manual

Safety light curtain
Hide thumbs Also See for F3SG-*RR Series:
Table of Contents

Advertisement

Setting

4. Setting with Rotary Switch/End Cap

4-1. Selecting Function with Rotary Switch
F3SG-RR series has the Rotary Switches to configure functions near the power cable. Configure functions
with the Rotary Switches before installing F3SG-RR in your site. Make sure to turn the power of the F3SG-
RR on after the setting with the Rotary Switches is complete.
Cascaded sensors are operated based on the Rotary Switches setting of the primary sensor. The Rotary
Switch setting of a secondary sensor does not affect the operation.
Function
Scan Code Selection
- Operate the Rotary Switches before turning the power of the F3SG-RR on.
- Both the emitter and receiver units must be set to the same code.
- A change of the Rotary Switches setting is activated upon power-on or lockout reset.
- If the Rotary Switch is operated during operation of the F3SG-RR, the F3SG-RR transitions to lockout.
4-2. Selecting Function with End Cap
F3SG-RR series has End Cap to configure the function at the opposite end from the power cable of the emit-
ter. Configure the function before installing the F3SG-RR in your site. Make sure to turn the power off the
F3SG-RR before replacing the End Cap.
Function
External Test Input Selection
- Do not remove the insulating rubber attached to the End Cap. Failure to do so may cause deterioration of the protective functions.
- When attaching the End Cap, tightly fasten the screw (M2.5, recommended torque: 0.35 N•m). Failure to do so may cause the
End Cap to come loose, leading to deterioration of the protective functions.
- The insulating rubber attached to connector of the End Cap may come off when removing the End Cap. If the rubber comes off,
place it back to the groove of the connector and insert the connector to the sensor body.
3
Wiring
Mounting/Beam Alignment
Position
Rotary Switch
Rotary Switch
End Cap
Black
White
Description
Code A
(factory default setting)
Code B
Description
24 V Active (factory default setting)
0 V Active
Operation check
F3SG-RR
Quick Installation Manual