5.2 FIRMWARE UPGRADE VERSION V7.00 OR HIGHER
5.2FIRMWARE UPGRADE VERSION V7.00 OR HIGHER
This section explains how to upgrade the F650 firmware code for version V7.00 or higher.
BOOT CODE RELEASE NOTES
It is mandatory to maintain version compatibility between firmware and boot code in the upgrade procedure, otherwise the
relay will not start after upgrading.
BEFORE PERFORMING THE UPGRADE PROCEDURE CHECK THAT BOOT AND FIRMWARE VERSION MATCH.
Firmware
7.12
7.20
1. Ethernet Connection/Type - Firmware upgrade processes require Ethernet communications. It is strongly recommended
to use a direct connection between the PC and the relay using a Cross-Over RJ45 Ethernet cable, instead a direct
connection through a hub or switch.
2. Relay IP Address - It must be assigned a IP address to the relay in the Ethernet parameters via HMI at PRODUCT
SETUP>COMMUNICATION>ETHERNET>ETHERNET
SETPOINT>PRODUCT SETUP>COMMUNICATION SETTINGS>NETWORK (Ethernet) E, A or B as shown in the Table
below.
Table 5–2: ETHERNET PARAMETERS
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET)
NAME
IP Address Oct1
IP Address Oct2
IP Address Oct3
IP Address Oct4
Netmask Oct1
Netmask Oct2
Netmask Oct3
Netmask Oct4
PRODUCT SETUP>COMMUNICATION SETTINGS >ROUTING
NAME
Default RT GWY Oct1
Default RT GWY Oct2
Default RT GWY Oct3
Default RT GWY Oct4
3. Example of IP Address Configuration:
5
The IP address and other parameters already assigned in the process will be:
IP Address:192.168.37.177
Netmask:255.255.255.0
Gateway:192.168.37.10
Note: To assure that the configuration is correctly setup it is possible to perform a ping command from the PC.
5-22
Bootware
7.12
7.12
E,
EVALUE
UNITS
192
168
37
177
255
255
255
0
EVALUE
UNITS
192
168
37
10
F650 Digital Bay Controller
5 BOOTCODE AND FIRMWARE UPGRADE
5.2.2 COMMUNICATION PARAMETERS
A
or
B
menu
or
via
RANGE
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
RANGE
[0 : 255]
[0 : 255]
[0 : 255]
[0 : 255]
5.2.1 INTRODUCTION
Enervista
7.20
7.20
Enervista
650
Setup
at
GEK-113000AE