Wiring diagram

Basic set-up

First, check the motor connection:
Please be ware the mechanical brake control cannot be trusted during this basic setup, therefore
control brake externally from the option until setup is finished. Also ensure that the motor can rotate
freely without causing damage or injury to personal.
1. Remove all signals to inputs 16-33 and I1-I8. Only Input 27(coast), I8 (q-stop), I3 (HW
limit) and I2 (HW limit) must be connected and high.
2. Select "Disable syncpos" in P700
3. Select "Local" function in Parameter 002. – VLT 5000 stops (display flashing)
4. Input the motor name plate data in P102-P106 and activate the "Automatic Motor
Adaptation" function in P107.
36
Positioning Controller