has been reached or the system is disarmed. If
alarm restores are enabled and swinger shutdown
is set to two, a restore will be reported if the sensor
is closed (normal state) at bell cutoff or becomes
closed after bell cutoff. If swinger shutdown is set
to one, a restore will only be sent if the sensor is
closed at the time of disarm. Restores are not sent
if a sensor is in swinger shutdown until the time of
disarm and the sensor is closed.
•
The default (0) prevents alarm restore reports.
•
To allow alarm restore reports, select enabled
(1).
Q-58 Select trouble restore reports
to CS (0-1)
DEFAULT: Enabled (1)
Trouble restore reports can be sent to the Central
Station when any sensor trouble condition clears.
•
The default (1) allows trouble restore reports.
•
To turn off trouble restore reports, select
disabled (0).
Q-59 Select bypass restores reports
to CS (0-1)
DEFAULT: Disabled (0)
Bypass restore reports can be sent to the Central
Station when any sensor that was force bypassed
or manually bypassed gets restored.
•
The default (0) prevents bypass restore
reports.
•
To allow bypass restore reports, select enabled
(1).
Q-60 Select AC restore reports to
CS (0-1)
DEFAULT: Enabled (1)
AC power restore reports can be sent to the Central
Station when the Control Panel regains AC power
after an AC power loss.
•
The default (1) allows AC power restore
reports.
•
To turn off AC power restore reports, select
disabled (0).
NOTE:
The AC power will have to be restored
to the Control Panel for one minute
before the AC power loss trouble alert
automatically clears. If programming
question Q‐39 is enabled, the actual AC
power restore report will occur at a
Control Panel Programming Questions
random time of up to four hours after the
AC power loss trouble alert
cleared.
The Control Panel's AC power icon
NOTE:
displays the power status. A red "X" over
the icon indicates no AC power.
Q-61 Select system low battery
restore reports to CS (0-1)
DEFAULT: Enabled (1)
Control Panel low battery restore reports can be
sent to the Central Station if the Control Panel
battery had tested low and is now Ok.
•
The default (1) allows Control Panel low
battery restore reports.
•
To turn off Control Panel low battery restore
reports, select disabled (0).
Q-62 Select RF low battery restores
reports to CS (0-1)
DEFAULT: Enabled (1)
Sensor low battery restore reports can be sent to
the Central Station if a sensor battery had tested
low and is now Ok.
•
The default (1) allows sensor low battery
restore reports.
•
To turn off sensor low battery restore reports,
select disabled (0).
Q-63 Select phone fail detect (0-1)
DEFAULT: Disabled (0)
The system can monitor the telephone line
connected to the Control Panel. If the telephone
line is shorted or cut, the Control Panel will indicate
telephone line trouble by sounding trouble beeps
and displaying the no‐phone icon.
If the optional cell radio modem is installed, the
telephone line failure will still be reported if this
question is enabled.
•
The default (0) disables this feature.
•
To turn on this feature, select enabled (1).
If the dialer is disabled with
NOTE:
programming question Q‐8, telephone
line failure detection is also disabled
regardless of the setting of this
programming question.
©2013 2GIG Technologies Inc. All Rights Reserved.
has
51
Need help?
Do you have a question about the Go Control and is the answer not in the manual?
Questions and answers