The dialer delay can be disabled per 
NOTE:
sensor without affecting SIA CP‐01 
compliance. See "RF Sensor Programming 
Steps" on page 30.
Q-36 Select burglary bell cutoff
(0-4)
DEFAULT: 4 minutes (0)
When a burglary alarm is triggered, the bell will 
sound until the burglary bell cutoff time expires.
The default (0) sets the burglary bell cutoff to 
4 minutes.
To change the burglary bell cutoff time, select 
(1), (2), (3), or (4).
Burglary Bell Cutoff Time
(0) 4 minutes
(1) 8 minutes
(2) 12 minutes
(3) 16 minutes
(4) Unlimited time
The 24‐hour Auxiliary Alarm Zone (08) 
NOTE:
does not follow the burglary bell cutoff 
time and will sound the Control Panel's 
local alarm until a User Code is entered. 
The Auxiliary Alarm Zone does not trigger 
the external siren (if used).
Q-37 Select fire bell cutoff (0-4)
DEFAULT: 4 minutes (0)
When a fire alarm is triggered, the bell sounds until 
the fire bell cutoff time expires.
The default (0) sets the fire bell cutoff time to 
4 minutes.
To change the fire bell cutoff time, select (1), 
(2), (3), or (4)
Fire Bell Cutoff Time
(0) 4 minutes
(1) 8 minutes
(2) 12 minutes
(3) 16 minutes
(4) Unlimited time
Q-38 Enter time to detect AC loss, in
minutes (0-30)
DEFAULT: 10 minutes (10)
AC power loss will cause an AC power loss alert 
 to be displayed, and the length of time before 
it is displayed can be set. When power returns, the 
Control Panel Programming Questions
time required before the AC power loss alert 
automatically clears is fixed at one minute.
The default (10) sets the AC power loss alert 
display time to ten minutes.
To change the AC power loss alert display 
time, enter (0‐30) minutes.
NOTE:
After the AC power alert 
displayed or clears, the AC power loss 
report or AC power restore report can be 
sent to the Central Station immediately, or 
at a random time, see Q‐39.
NOTE:
The Control Panel's AC power icon 
displays the power status immediately. A 
red "X" over the icon indicates no AC 
power.
Q-39 Select random AC loss report
time (0-1)
DEFAULT: Enabled (1)
This feature allows the system to report AC power 
loss and AC power restore at a random time of up 
to 45 minutes after the event occurs. This helps to 
reduce Central Station congestion due to a wide‐
spread power outage affecting many Control Panels 
at once. The random AC power status report timer 
is triggered based on the time set by Q‐38.
The default (1) allows random timed AC power 
reports.
To turn off random timed AC power reports, 
select disabled (0).
Q-40 Enter CS #2 phone number (0-
25 digits)
DEFAULT: No default
The telephone number for Central Station #2 can 
be up to 25 digits. Central Station telephone #2 is 
dialed as backup in case telephone #1 does not 
connect.
Enter the Central Station #2 telephone 
number.
The Shift button accesses the pound and star 
symbols. The P button adds a 3‐second pause 
to the dialing.
Q-41 Enter CS #2 account number
(4 digits)
DEFAULT: No default
The account number for Central Station #2 is 
always four digits and can include some alpha 
characters.