4.1.6.3 INRUSH CURRENT THRESHOLDS

A third Thresholds screen, displayed by pressing the
button, defines the inrush current thresholds. This involves
setting the triggering threshold and the inrush current capture stopping threshold (the stopping threshold being the
triggering threshold less the hysteresis).
Figure 4-18
To change the inrush current triggering threshold:
■ Press the
button.
■ Use the arrow buttons to change the triggering threshold. The unit can be A, kA, or mA.
■ Press
, then use the ▲ and ▼ arrows to highlight the hysteresis in yellow.
■ Use the navigation buttons to change the hysteresis.
For more information on the hysteresis, refer to § A.1. Configuring hysteresis at 100% is equivalent to not having a stop
threshold (see § A.1.6)
Confirm your selections by pressing
. To return to the Configuration menu, press
.
NOTE: You cannot modify thresholds in the transient mode if the instrument is searching for transients.
33
Power Quality Analyzer PowerPad
III Model 8336
®