4.1.3 CALCULATION METHODS

The Calculation Methods menu X
■ Breakdown or no breakdown of the non-active quantities
■ Unit of energy
■ Reference for the level of harmonics of the phases
■ Coefficients of calculation for the K factor
■ Method of calculation of the long-term flicker

4.1.3.1 NON-ACTIVE QUANTITIES

The var menu is used to choose whether to separate or combine the non-active quantities (power and energy).
Use the ▲ and ▼ buttons to select Separated or Combined.
■ Separated: Non-active power N is separated into reactive power (fundamental) Q1 and distorting power D. Non-active
energy Nh is separated into Q1h and Dh.
■ Combined: Non-active power N and non-active energy Nh are displayed.
Press
to confirm the selection and return to the Configuration menu.
NOTE: This setting cannot be modified when the instrument is recording, metering energy, and/or searching for
alarms.