5.2.3 APPARENT POWER
The S sub-menu displays the harmonics of the apparent power, for all connections except 3-wire 3-phase. The horizontal
axis indicates the orders of the harmonics. The bars of the bar chart above the horizontal center line signify harmonic
power consumed, those below it harmonic power generated.
3L APPARENT POWER HARMONICS
Item Function
S-h03: harmonic number
%: level of harmonics with fundamental apparent power (%f) or (total) apparent power (%r) as reference
1
+006°: phase shift of voltage harmonic with respect to current harmonic
: energy generated for this harmonic
: energy consumed for this harmonic
2
Harmonic selection cursor; change values with the cursor using the ◄ and ►buttons
Horizontal axis indicates orders of harmonics.
Harmonic level is percentage of fundamental apparent or (total) apparent power
3
Range DC: DC component
1 to 25: harmonics of order 1 to 25. When cursor exceeds order 25, order 26 to 50 appears
L1 APPARENT POWER HARMONICS
1
2
Power Quality Analyzer PowerPad
1
2
III Model 8336
®
Figure 5-20
Figure 5-21
3
3