9.2.7 CURRENT PROBES AND SENSORS

When installing probes, face the arrow on the probe in the direction of the load. Note that only AmpFlex
watertight; all other probes and sensors are non-watertight.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Ø
Safety
NOTE: Currents <0.5A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Ø
Safety
NOTE: Currents <0.5A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Ø
Safety
NOTE: Currents <1A
AC/DC
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Ø
Safety
The 5A range of the MN193 is designed to work with secondary current transformers.
Best accuracy is available when entering the transformer ratio (e.g. 1000/5A). When used to measure 5A direct, the
resolution will be limited to 0.1A max.
NOTE: Currents < (Primary x 5) ÷ (Secondary x 1000) or <250mA on the 5A range and <0.2A on the 100A range will be
displayed as zero with this probe. Power calculations will also be zeroed when the current is zeroed.
Nominal Range
Measurement Range
Probe Output Signal*
Sensor
Safety
*Output is proportional to the amplitude and frequency of the measured current.
NOTE: Currents <10A will be displayed as zero. Neutral current measures down to 0A (if 6500A or 10kA is selected)
Currents <100mA will be displayed as zero. Neutral current measures down to 0A (if 100A is selected)
128
1000A
for f ≤1kHz
AC
1A to 1200A
max (I >1000A not continuously)
AC
1mV
/A
AC
AC
2" (52mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
for f ≤1kHz
200A
AC
2A to 240A
max (I >200A not permanent)
AC
5mV
/A
AC
AC
0.8" (20mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
1000A
, 1400A
max
AC
DC
10A to 1000A
, 10A to 1300A
AC
1mV/A
One 1.6" (42mm) or two 0.98" (25.4mm) or
two bus bars 1.96 x 0.19" (50 x 5mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
will be displayed as zero. Neutral current measures down to 0A.
5A and 100A
AC
5A: 0.005A to 6A
max (1A to 1200A with ratio 1000/5 selected)
AC
100A: 0.1A to 120A
max
AC
5A: 200mV/A
; 100A: 10mV/A
AC
0.8" (20mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
3000A
AC
100mA to 10kA
140mV
/3000A
at 60Hz (117.3mV
AC
AC
Length = 24" (610mm); Ø = 7.64" (190mm)
Length = 36" (910mm); Ø = 11.46" (290mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
Model SR193
Model MN93
Model MR193
PEAK AC+DC
Model MN193
AC
AmpFlex
Sensors
®
/3000A
at 50Hz)
AC
AC
sensors are
®
Power Quality Analyzer PowerPad
III Model 8336
®