Harmonics Mode; Phase-To-Neutral Voltage Harmonics - AEMC PowerPad III 8336 User Manual

3-phase power quality analyzer
Hide thumbs Also See for PowerPad III 8336:
Table of Contents

Advertisement

5.2 HARMONICS MODE

The Harmonics mode displays a representation of the harmonic levels of the voltage, current, and apparent power, order
by order. It can be used to determine the harmonic currents produced by nonlinear loads, and analyze problems caused
by harmonics according to their order (overheating of neutrals, conductors, motors, and so on).
● V - Phase-to-neutral voltage
● A - Harmonics of the current
● S - Apparent power of the harmonics
● U - Phase-to-phase voltage harmonics
● The
and

5.2.1 PHASE-TO-NEUTRAL VOLTAGE HARMONICS

The V sub-menu displays the harmonics of the phase-to-neutral voltage only for sources having a neutral.
NOTE: The choice of curves to be displayed depends on the type of connection (see § 4.1.4):
● Single-phase, 2-wire: no choice (L1)
● Single-phase, 3-wire: L1, N
● Split-phase, 3-wire: 2L, L1, L2
● Split-phase, 4-wire: 2L, L1, L2, N
● 3-phase, 4-wire: 3L, L1, L2, L3, -,+
● 3-phase, 5-wire: 3L, L1, L2, L3, N, -,+
The examples shown in the following sections were obtained with a 5-wire 3-phase connection.
Power Quality Analyzer PowerPad
buttons allow the user to zoom in or out, in increments of 2%, 5%, 10%, 20%, 50% and 100%.
III Model 8336
®
Figure 5-15
51