5.1.2 INRUSH CURRENT MODE

While in Waveform
and current waveforms, network frequency, half-cycle RMS voltages and currents except for the neutral) and to view and
delete the recordings.
When Inrush Current mode is selected, the screen displayed will depend on the following conditions:
if ...
no capture has been made
captures have been made

5.1.2.1 PROGRAMMING A CAPTURE

To program the capture of an Inrush current, proceed as follows:
■ At the Waveform Capture screen (Figure 5-1), select Inrush Current. The Capture Schedule screen is displayed.
Item Function
1
Icons for the mode and sub-mode.
2
Rapid programming and start of capture.
3
Shortcut to the Configuration menu to set triggering thresholds.
When triggering filter appears in red it is not available due to incompatibility with the configuration (connection, type of sensors, or
4
current ratio).
5
Displays the parameters of the capture.
6
Programs the capture.
: confirms programming of a capture.
7
: deletes a capture (this icon is displayed if a capture has been made).
To quickly start recording, press the
hysteresis of 100%. Note that the rapid starting of an inrush current modifies the configuration of the current threshold.
To program a capture, enter the triggering filter (3A, A1, A2, or A3), the start date and time, and the recording mode (RMS
+ PEAK or RMS only).
● The RMS + PEAK recording mode is used to produce a trend recording of the half-period RMS values and a
trend recording of the samples (envelopes and waveforms). The maximum duration of such a recording depends
on the network frequency; on average the duration is approximately one minute.
● In the RMS only recording mode, the recording of the samples is eliminated in favor of a longer maximum capture
duration. This mode records only the half-period RMS values and its maximum duration is about ten minutes.
Power Quality Analyzer PowerPad
mode, the Inrush current
then ...
the Capture Schedule screen is displayed
the Capture Parameters screen is displayed
1
2
3
button. Recording starts immediately with a current threshold of 0A and a
III Model 8336
®
sub-mode is used to capture (record) Inrush currents (voltage
Figure 5-6
4
5
6
7
45