Current Probes And Sensors - AEMC 8230 User Manual

Powerpad jr. single-phase power quality analyzer
Table of Contents

Advertisement

3.2.5

Current Probes and Sensors

When installing probes, face the arrow on the probe in the direction of the load.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Diameter
Safety
NOTE: Currents <0.5A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Diameter
Safety
NOTE: Currents <0.5A will be displayed as zero. Neutral current measures down to 0A.
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Diameter
Safety
NOTE: Currents <1A
AC/DC
Nominal Range
Measurement Range
Probe Output Signal
Maximum Clamping Diameter
Safety
The 5A range of the MN193 is designed to work with secondary current transformers.
Best accuracy is available when entering the transformer ratio (e.g. 1000/5A). When used to measure 5A
direct, the resolution will be limited to 0.1A max.
NOTE: Currents < (Primary x 5) ÷ (Secondary x 1000) or <250mA on the 5A range and <0.2A on the 100A
range will be displayed as zero with this probe. Power calculations will also be zeroed when the current is
zeroed when the current is zeroed.
Power Quality Analyzer Model 8230
Model SR193
for f ≤1kHz
1000A
AC
1A to 1200A
1mVAC/A
AC
2" (52mm)
EN 61010-2-032, Pollution Degree 2, 600V CAT IV, 1000V CAT III
Model MN93
for f ≤1kHz
200A
AC
2A to 240A
AC
5mV
/A
AC
AC
0.8" (20mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
Model MR193
1000A
, 1400A
AC
10A to 1000A
1mV/A
One 1.6" (42mm) or two 0.98" (25.4mm) or
two bus bars 1.96 x 0.19" (50 x 5mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
will be displayed as zero. Neutral current measures down to 0A.
Model MN193
5A and 100A
5A: 0.005A to 6A
100A: 0.1A to 120A
5A: 200mV/A
0.8" (20mm)
EN 61010-2-032, Pollution Degree 2, 300V CAT IV, 600V CAT III
max (I >1000A not continuously)
AC
max (I >200A not permanent)
max
DC
, 10A to 1300A
AC
PEAK AC+DC
AC
max (1A to 1200A with ratio 1000/5 selected)
AC
max
AC
; 100A: 10mV/A
AC
AC
17