ABB REO 517 Applications Manual page 96

Multi-function terminals for railway application
Table of Contents

Advertisement

86
Time delayed phase and residual
overcurrent protection (TOC1)
The duration of each output signal is at least 15 ms. This enables continuous output sig-
nals for current, which go just a little above the set operating value.
The timer tP is activated if the current in any of the phases exceeds the set operate value
I>. The output signal TOC1-TRIP is activated if the current exceeds the set operate val-
ue for a period longer than the set time-delay tP.
The timer tN is activated if the residual current exceeds the set operate value IN> for
the earth-fault protection function. The output signal TOC1-TRIP is activated if the cur-
rent exceeds the set operate value for a period longer than the set time-delay tN.
The simplified logic diagram of the time delayed phase overcurrent functions is shown
in figure 43.
The function is disabled (blocked) if:
The terminal is in TEST mode (TEST-ACTIVE is high) and the function has been
blocked from the HMI (BlockTOC1=Yes).
The input signal TOC1-BLOCK is high.
The TOC1-BLOCK blocking signal can be connected to a binary input of the terminal
in order to receive a block command from external devices or can be software connect-
ed to other internal functions of the terminal itself in order to receive a block command
from internal functions. Through an OR gate it can be connected to both binary inputs
and internal function outputs. The TOC1-BLOCK signal blocks also the time delayed
residual overcurrent function (IN>).
With the setting Operation=Independ (independent function) the protection function is
constantly active. With the setting Operation=Backup the binary input signal TOC1-
RELEASE must be activated to receive a logical one to the AND-gate and thereby en-
able the protection function.