Interlocking
6LJQDOV LQ GRXEOHEUHDNHU DUUDQJHPHQW
The busbar earthing switch is only allowed to operate if all disconnectors of the bus sec-
tion are open.
Section 1
A1
B1
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
DB_BUS
)LJXUH %XVEDUV GLYLGHG E\ EXVVHFWLRQ GLVFRQQHFWRUV FLUFXLW EUHDNHUV
To derive the signals:
6LJQDO
ABCDC_OP
Signal if all disconnectors of this busbar section are open.
VP_ABCDC
The switch status of ABCDC is valid.
EXDUP_BB
Signal if there is no transmission error from any bay that contains the above
information.
These signals from each double-breaker bay (DB_BUS) are needed:
6LJQDO
Q1OPTR
Signal if Q1 is open.
Q2OPTR
Signal if Q2 is open.
VPQ1TR
The switch status of Q1 is valid.
VPQ2TR
The switch status of Q2 is valid.
EXDUP_DB
Signal if there is no transmission error from the bay that contains the above
information. This signal is taken from the data valid output on the command
function block.