Interlocking
and bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:
6LJQDO
Signal if there is no transmission error from the bay that contains the above
information. This signal is taken from the data valid output on the command
function block.
For bus-coupler bay n, these conditions are valid:
Q1Q2OPTR (bay 1)
Q1Q2OPTR (bay 2)
. . .
. . .
Q1Q2OPTR (bay n-1)
VPQ1Q2TR (bay 1)
VPQ1Q2TR (bay 2)
. . .
. . .
VPQ1Q2TR (bay n-1)
. . .
. . .
)LJXUH  6LJQDOV IURP DQ\ ED\V LQ EXVFRXSOHU ED\ Q
If the busbar is divided by bus-section disconnectors into bus sections, the signals
BBTR are connected in parallel - if both bus-section disconnectors are closed. So for
the basic project-specific logic for BBTR above, add this logic:
&
&
EXDUP_AB
&
99000364.vsd
&KDSWHU 
&RQWURO