ABB REO 517 Applications Manual page 265

Multi-function terminals for railway application
Table of Contents

Advertisement


Interlocking
Q75_OP = 1
Q75_CL = 0
BC_AB_CL = 0
If there is no second busbar B and therefore no Q20 and Q2 disconnectors, then the in-
terlocking for Q20 and Q2 are not used. The states for Q20, Q2, Q25, BC_AB, BBTR
are set to open by setting the appropriate module inputs as follows. In the functional
block diagram, 0 and 1 are designated 0=FIXD-OFF and 1=FIXD-ON:
Q20_OP = 1
Q20_CL = 0
Q2_OP = 1
Q2_CL = 0
Q25_OP = 1
Q25_CL = 0
BC_AB_CL = 0
BBTR_OP = 1
,QWHUORFNLQJ IRU WUDQVIRUPHU ED\
The interlocking module AB_TRAFO is used for a transformer bay connected to a dou-
ble busbar arrangement according to figure 131. The module is used when there is no
disconnector between circuit breaker and transformer. Otherwise, the module
ABC_LINE can be used. This module can also be used for a single busbar arrangement.
&KDSWHU 
&RQWURO
255