ABB REO 517 Applications Manual page 234

Multi-function terminals for railway application
Table of Contents

Advertisement


224
Apparatus control
From remote-
control gateway
SingleCmdFunc
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
Defined as pulse outputs
)LJXUH  &RQWURO FRPPDQGV IURP UHPRWHFRQWURO JDWHZD\
/RFDO SDQHO EDFNXS SDQHO
The connection of an external local panel to the apparatus control modules is done via
binary inputs. Figure 105 shows one example of a solution. This solution of local con-
trol considers the interlocking function. The panel can also be used as an back-up panel,
but the outputs from the panel are then connected directly to the high-voltage appara-
tuses. The position indications are normally directly connected to the panel to get inde-
pendent information about the apparatus positions. At use as back-up panel, the select
and execute inputs into the control terminal must be blocked, for example, with AND
gates with the condition no back-up.
Apparatus 1
R_SEL_O
R_SEL_C
R_OPEN
R_CLOSE
.
R_CANCEL
.
To other apparatus
.
in the bay
.
COMCON
99000336.vsd
&KDSWHU 
&RQWURO