Number of reclosing attempts: 1 to 4 attempts can be chosen. In most cases 1 attempt is
sufficient as the majority of arcing faults will cease after the first reclosing shot. In pow-
er systems with many faults caused by other phenomena than lightning, for example
wind, it can be motivated with more than one reclosing attempt.
If a permissive channel is used between the line ends, and the availability of the com-
munication channel is considered to be low, extended dead time in case of loss of the
channel should be used.
Typical required dead time for three pole trip and reclosing is 400 ms. Different local
phenomena, such as moisture, salt, pollution, etc. can influence the required dead time.
The open time for the first auto-reclosing shot can be set three pole (t1).