ABB REO 517 Applications Manual page 325

Multi-function terminals for railway application
Table of Contents

Advertisement

Disturbance report (DRP)
2SHUDWLRQ
2II
Disturbances are not stored.
LED information (yellow - start, red - trip) is not stored or changed.
No disturbance summary is scrolled on the local HMI.
2SHUDWLRQ
2Q
Disturbances are stored, disturbance data can be read from the local HMI and from
a front-connected PC or Station Monitoring System (SMS).
LED information (yellow - start, red - trip) is stored.
The disturbance summary is automatically scrolled on the local HMI for the two lat-
est registered disturbances, until cleared.
Post re-trigger can be set to On or Off
3RVWUHWULJ
2Q
Re-trigger during the set post-fault time is enabled.
3RVWUHWULJ
2II
Re-trigger during the set post fault time is not accepted.
6HTXHQFH QXPEHU
Normally, this setting option is seldom used. Each disturbance is assigned a number in
the disturbance report. The first disturbance each day normally receives 6HTXHQFH1R
. The value of 6HTXHQFH1R that can be read in the service report is the number that will
be assigned to the next disturbance registered during that day.
In normal use, the sequence number is increased by one for each new disturbance until
it is reset to zero each midnight.
5HFRUGLQJ WLPHV
The different recording times for the disturbance report are set (the pre-fault time, post-
fault time, and limit time). These recording times affect the disturbance recorder and
event recorder functions. The total recording time, tRecording, of a recorded distur-
bance is:
tRecording =
tPre + tFault + tPost, or tPre + tLim, depending on which criterion stops the
current disturbance recording.
&KDSWHU 
0RQLWRULQJ
315

Advertisement

Table of Contents
loading

Table of Contents