Interlocking
6LJQDOV IURP EXV FRXSOHU
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-bus-
bar connection could exist via the bus-section disconnector and bus-coupler within the
other bus section.
Section 1
A1
B1
C
ABC_LINE
ABC_BC
)LJXUH  %XVEDUV GLYLGHG E\ EXVVHFWLRQ GLVFRQQHFWRUV FLUFXLW EUHDNHUV
To derive the signals:
6LJQDO
BC_AB_CL
Signal if a bus-coupler connection exists between busbar A and B.
BC_AC_OP
Signal if there is no bus-coupler connection between busbar A and C.
BC_AC_CL
Signal if a bus-coupler connection exists between busbar A and C.
BC_BC_OP
Signal if there is no bus-coupler connection between busbar B and C.
BC_BC_CL
Signal if a bus-coupler connection exists between busbar B and C.
VP_BC_AB
The switch status of BC_AB is valid.
VP_BC_AC
The switch status of BC_AC is valid.
VP_BC_BC
The switch status of BC_BC is valid.
EXDUP_BC
Signal if there is no transmission error from bay BC (bus-coupler bay).
These signals from each bus-coupler bay (ABC_BC) are needed:
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_LINE
A2
B2
C
ABC_BC