ABB REO 517 Applications Manual page 371

Multi-function terminals for railway application
Table of Contents

Advertisement

Monitoring of DC analog measurements
&RPELQDWLRQ RI SHULRGLF UHSRUWLQJV
The reporting of the new value depends on setting parameters for the dead-band and for
the periodic reporting. Table 1 presents the dependence between different settings and
the type of reporting for the new value of a measured quantity.
7DEOH  'HSHQGHQFH RI UHSRUWLQJ RQ GLIIHUHQW VHWWLQJ SDUDPHWHUV
(Q'HDG% (Q,'HDG% (Q'HDG%3
Off
Off
Off
On
On
Off
On
On
Off
On
On
Off
5HS,QW 5HSRUWLQJ RI WKH QHZ YDOXH
Off
0
On
t>0
On
t>0
On
t>0
Off
0
Off
0
No measured values is reported
The new measured value is reported
only if the time t period expired and if,
during this time, the integrating dead-
band limits were exceeded (periodic
reporting with integrating dead-band
supervision in series)
The new measured value is reported
only if the time t period has expired and
if, during this time, the amplitude dead-
band limits were exceeded (periodic
reporting with amplitude dead-band
supervision in series)
The new measured value is reported
only if the time t period expired and if at
least one of the dead-band limits were
exceeded (periodic reporting with
dead-band supervision in series)
The new measured value is reported
only when the integrated dead-band
limits are exceeded
The new measured value is reported
only when the amplitude dead-band
limits were exceeded
&KDSWHU 
0RQLWRULQJ
361