ABB REO 517 Applications Manual page 138

Multi-function terminals for railway application
Table of Contents

Advertisement


128
Breaker failure protection (BFP)
)LJXUH  %UHDNHUIDLOXUH SURWHFWLRQ
High-
Current
pass
samples
filtering
)LJXUH  &XUUHQW GHWHFWRU $6' DQG 506 PHDVXUHPHQW
5HWULS IXQFWLRQV
The retrip function of the original circuit breaker is set at one of three options:
6HWWLQJ
7KH UHWULS
Off
function is not executed.
I> check
occurs with a current check.
No I> check
occurs without a current check.
The retrip timer t1 can be set from 0 to 60 s.
A trip pulse, tp, is generated with a length of 150 ms.
%DFNXS WULS
The back-up trip delay timer t2 can be set between 0 and 60 s.
A trip pulse, tp, is generated with a length of 150 ms.
'HVLJQ
The breaker failure protection is initiated by the trip commands from the protection
functions, either internal to the terminal or from external commands through binary in-
puts. The start can be initiated by a general signal, or in some cases phase selective sig-
nals.
Creation of
Recti-
stabilizing
fying
signal
RMS
calculation
Decision
through
ASD
comparison
Decision
through
RMS
comparison
en00000011.vsd
&KDSWHU 
&XUUHQW