ABB REO 517 Applications Manual page 145

Multi-function terminals for railway application
Table of Contents

Advertisement

Unbalance protection for capacitor banks
(TOCC)
rent of stage IHigh is low compared to the earth fault current in the system. The current
stage I>Low is normally set to give alarm at 50% of the set operate current of stage
I>High.
The calculation of settings for the unbalance protection function must take into consid-
eration how the capacitor bank is built up and it is often made by aids of a computer
program.
6HWWLQJ RI UHOD\ RSHUDWLQJ FXUUHQWV
If Is is the primary setting operating value of the function, then the secondary setting
current (Is
) is:
SEC
I
S EC
Is
------------- - Is
=
SEC
I
PRIM
where I
is the secondary rated current of the main CT and I
SEC
current of the main CT.
The relay setting value is given in percentage of the secondary base current value, I
associated to the current transformer input I5. The value for I>Low and I>High is given
from the formula:
Is
SEC
------------- - 100
I
=
set
I
5b
&KDSWHU 
&XUUHQW
(Equation 61)
is the primary rated
PRIM
5b
(Equation 62)
135
,