ABB REO 517 Applications Manual page 258

Multi-function terminals for railway application
Table of Contents

Advertisement

248
Interlocking
3DUDPHWHU VHWWLQJ
If there is no bypass busbar and therefore no Q7 disconnector, then the interlocking for
Q7 is not used. The states for Q7, Q75, C_DC, BC_AC, BC_BC are set to open by set-
ting the appropriate module inputs as follows. In the functional block diagram, 0 and 1
are designated 0=FIXD-OFF and 1=FIXD-ON:
Q7_OP = 1
Q7_CL = 0
Q75_OP = 1
Q75_CL = 0
C_DC_OP = 1
BC_AC_OP = 1
BC_AC_CL = 0
BC_BC_OP = 1
BC_BC_CL = 0
EXDU_BPB = 1
VP_C_DC = 1
VP_BC_AC = 1
VP_BC_BC = 1
If there is no second busbar B and therefore no Q2 disconnector, then the interlocking
for Q2 is not used. The state for Q2, Q25, BC_AB, BC_BC are set to open by setting
the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are
designated 0=FIXD-OFF and 1=FIXD-ON:
Q2_OP = 1
Q2_CL = 0
Q25_OP = 1
Q25_CL = 0
BC_AB_CL = 0
BC_BC_OP = 1
BC_BC_CL = 0
VP_BC_AB = 1