ABB REO 517 Applications Manual page 177

Multi-function terminals for railway application
Table of Contents

Advertisement


Synchro-check and energising-check
(SYRW)
)XQFWLRQDOLW\
Connectable inputs
General Block
From f use f ailure
detection, line side
(external or internal)
From f use f ailure
detection bus side
)LJXUH  ,QSXW DQG RXWSXW VLJQDOV
6\QFKURFKHFN
Description of input and output signals for the synchrocheck function.
,QSXW VLJQDOV
'HVFULSWLRQ
SYRW-BLOCK
General block input from any external condition, that should block the
synchrocheck
SYRW
SYRW-BLOCK
SYRW-VTSU
SYRW-UB1FF
SYRW-UB1OK
FreqDiff < 50-300 mHz
PhaseDiff< 5-75 deg
UDiff <5-60% U1b
ULHigh>30-100% U1b
UBHigh>30-100% U1b
ULow < 10-100 % U1b
SYRW-AUTO
SYRW-MANOK
&KDSWHU 
&RQWURO
Connectable
outputs
en02000567.vsd
167