Terminal identification and base values
where:
I
= secondary rated current of the main CT
SEC
I
= primary rated current of the main CT
PRIM
Is
= primary setting value of the current
The relay setting value IP>> is given in percentage of the secondary base current value,
Ixb, associated to the current transformer input Ix:
Is
SEC
⋅
IP>>
=
------------- - 100
Ixb
The value of Ixb can be calculated as:
Rated primary current
Ixb
--------------------------------------------------------- -
=
CT ratio
The voltage transformer secondary setting voltage (Us
U
SEC
⋅
--------------- - Us
Us
=
SEC
U
PRIM
where:
U
secondary rated voltage of the main VT
SEC
U
primary rated voltage of the main VT
PRIM
Us
primary setting value of the voltage
The relay setting value UPE< is given in percentage of the base voltage value, Uxb, as-
sociated to the voltage transformer input Ux:
&KDSWHU
*HQHUDO
(Equation 11)
(Equation 12)
) is:
SEC
(Equation 13)