Apparatus control
The apparatus control handles different kind of commands coming from different oper-
ator places. Interpret the local operator place as the back-up panel.
5HPRWH
These commands are supported from remote operator place:
•
Select, open/close
•
Execute, open/close
•
Cancel the selection
6WDWLRQ
These commands are supported from the station HMI:
•
Select, open/close
•
Execute, open/close
•
Cancel the selection
•
Block/deblock operation (per apparatus or bay)
•
Override of reservation, interlocking and/or synchro-check/phasing
•
Selection of operator place, station and/or remote
•
Block/deblock updating of the position indications (per apparatus or bay)
•
Setting of the position indication, open/close
/RFDO
These commands are supported from the local HMI (back-up panel):
•
Select, open/close
•
Execute, open/close
•
Override, reservation and/or interlocking
•
Set operator place to local (switch on the back-up panel)
$XWRPDWLF IXQFWLRQV
An automatic program (placed in the control terminal or in external equipment) can be
connected to the apparatus control. These signals can be connected to the apparatus con-
trol:
•
Signals for select (open/close)
•
Signals for execute (open/close)
•
Cancel the selection
•
Signal to reserve the apparatus for automatic functions. Used when the apparatus is
included in a sequence
&KDSWHU
&RQWURO
189