ABB REO 517 Applications Manual page 208

Multi-function terminals for railway application
Table of Contents

Advertisement

198
Apparatus control
With the inputs (S_R, S_S, L_L) that are obtained, the desired operator place can be se-
lected. It has a built-in priority with Local as highest, Station as intermediate, and Re-
mote as lowest priority. When two or more inputs are set at the same time, the higher
priority prevails. The inputs S_R and S_S have pulse inputs, but the L_L requires a
steady signal. Figure 84 shows the logic:
S_R
S_S
L_L
)LJXUH  7KH RSHUDWRU SODFH VHOHFWLRQ UHSUHVHQWHG E\ ORJLF
If the operator place selection is used without any priority and if the outputs REMOTE/
STATION/LOCAL can be set independent of each other, the inputs REMOTE/STA-
TION/LOCAL on COMCON can be used. See configuration example in the section of
"Operator place selection" in "Configuration".
5HVHUYDWLRQ DQG VHOHFWLRQ
The purpose of the reservation and selection function is primarily to transfer interlock-
ing information in a safe way and to prevent double operation in a bay, switchgear, or
complete substation. The section of "Reservation function" in "Configuration" de-
scribes the method and the meaning of the inputs and outputs of BAYCON.
,QIRUPDWLRQ H[FKDQJH
The input EXCH_IN and output EXCH_OUT are used for information exchange be-
tween BAYCON elements, when more than eight apparatuses in the same bay are used
for control. The inputs and outputs of these elements are connected to each other in a
loop as shown in figure 85.
The reservation and selection function has several bits available to request other BAY-
CONs to be reserved. These BAYCONs reply with an acknowledge through the same
information exchange.
Only BAYCONB, and BAYCONF have this functionality.
&
S
Q
R
Q
&
&KDSWHU 
REMOTE
&
STATION
&
LOCAL
99000127.vsd
&RQWURO

Advertisement

Table of Contents
loading

Table of Contents