ABB REO 517 Applications Manual page 301

Multi-function terminals for railway application
Table of Contents

Advertisement

Event function (EV)
5HSRUW DOO HYHQWV means that all events, that are set to OnSet/OnReset/OnChange are re-
ported as OnChange, that is, both at set and reset of the signal. For double indications
when the suppression time is set, the event ignores the timer and is reported directly.
Masked events are still masked.
Parameters to be set for the event function block are:
T_SUPRyy including the suppression time for double indications.
NAMEyy including the name for each input.
PrColxx including the type of protocol for sending the events.
INTERVAL used for the cyclic sending of data.
BOUND telling that the block has connections to other terminals over the LON bus.
FuncTEVx (for EV01-EV06) including the function type for sending events via
IEC 60870-5-103.
InfoNoyy (for EV01-EV06) including the information number for the events send-
ing via IEC 60870-5-103.
These parameters are set from the CAP configuration tool. When the BOUND param-
eter is set, the settings of the event masks have no meaning.
&KDSWHU 
/RJLF
291