In figure 108 to figure 111, the SY_FAIL input supervises the synchronization time. If
the relay does not reach synchronism within a certain time, SY_FAIL is activated and
resets the complete operation sequence.
$XWRUHFORVLQJ
Figure 112 shows the interaction between the autoreclosing (AR) module and the appa-
ratus control modules. The OR gate for the close signal must have the same execution
cyclicity as the autoreclosing module. The signal BLK_AR from SWICON is used to
block the autoreclose function at the moment the circuit breaker is under operation.