ABB REO 517 Applications Manual page 327

Multi-function terminals for railway application
Table of Contents

Advertisement

Disturbance report (DRP)
7DEOH  'LVWXUEDQFH UHSRUW VHWWLQJV
2SHUDWLRQ 'LVWXUE
6XPPDU\
Off
Off
Off
On
On
On or Off
7KHQ WKH UHVXOWV DUH
Disturbances are not stored.
LED information is not displayed on the HMI and not stored.
No disturbance summary is scrolled on the HMI.
Disturbances are not stored.
LED information (yellow - start, red - trip) are displayed on the
local HMI but not stored in the terminal.
Disturbance summary is scrolled automatically on the local
HMI for the two latest recorded disturbances, until cleared.
The information is not stored in the terminal.
The disturbance report works as in normal mode.
Disturbances are stored. Data can be read from the local HMI,
a front-connected PC, or SMS.- LED information (yellow - start, red
- trip) is stored.
The disturbance summary is scrolled automatically on the
local HMI for the two latest recorded disturbances, until cleared.
All disturbance data that is stored during test mode remains in
the terminal when changing back to normal mode.
&KDSWHU 
0RQLWRULQJ
317