ABB REO 517 Applications Manual page 299

Multi-function terminals for railway application
Table of Contents

Advertisement

Event function (EV)
Each event function block has 16 connectables corresponding to 16 inputs INPUT1 to
INPUT16. Every input can be given a name with up to 19 characters from the CAP con-
figuration tool.
The inputs can be used as individual events or can be defined as double indication
events.
The inputs can be set individually from the Parameter Setting Tool (PST) under the
Mask-Event function as:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
Also an input PrColxx (xx=01-44) is available on the function block to define on which
protocol the events shall be sent.
The event function blocks EV01-EV06 have inputs for information numbers and func-
tion type, which are used to define the events according to the communication standard
IEC 60870-5-103.
'RXEOH LQGLFDWLRQ
Double indications are used to handle a combination of two inputs at a time, for exam-
ple, one input for the open and one for the close position of a circuit breaker or discon-
nector. The double indication consists of an odd and an even input number. When the
odd input is defined as a double indication, the next even input is considered to be the
other input. The odd inputs has a suppression timer to suppress events at 00 states.
To be used as double indications the odd inputs are individually set from the SMS under
the Mask-Event function as:
Double indication
Double indication with midposition suppression
Here, the settings of the corresponding even inputs have no meaning.
These states of the inputs generate events. The status is read by the station HMI on the
status indication for the odd input:
00 generates an intermediate event with the read status 0
01 generates a close event with the read status 1
10 generates an open event with the read status 2
&KDSWHU 
/RJLF
289