Logic function blocks
Fast logic
Function 1
&
)LJXUH  ([DPSOH RI ORJLF ZLWK V\QFKURQL]HG VLJQDOV
MOFn and MOLn, n=1-3, have 16 inputs and 16 outputs. Each INPUTm is copied to
the corresponding OUTPUTm, where m presents the serial number of the input and the
output in the block. The MOFn are the first blocks and the MOLn are the last blocks in
the execution order in the slow logic.
&DOFXODWLRQV
For the AND gates, OR gates, inverters, normal SR (Set-Reset) flip-flops, XOR gates
and MOVE elements no settings exist.
For the normal On/Off delay timers and pulse timers the time delays and pulse lengths
are set from the CAP configuration tool.
Both timers in the same logic block (the one delayed on pick-up and the one delayed on
drop-out) always have a common setting value. Setting values of the pulse length are
independent of one another for all pulse circuits.
For the controllable gates, settable timers, SR flip-flops with/without memory the set-
ting parameters are accessible through the HMI and SMS.
&RQILJXUDWLRQ
The configuration of the logics is performed from the CAP configuration tool.
Execution of functions as defined by the configurable logic blocks runs in a fixed se-
quence in two different cycle times, typical 6 ms and 200 ms.
Slow logic
MOFn
Function 2
MOVE
Function 3
&KDSWHU 
&RPPRQ IXQFWLRQV
Fast logic
MOLn
&
MOVE
xx00000541.vsd