Apparatus control
Allowed time from selection to feedback select.
7B67$57
Allowed time from execute to position indication change. Supervises the time for posi-
tion change from 01 -> 00 or 10 -> 00.
7B38/6(
Time parameter for command output pulse length. T_PULSE = 0 gives a steady com-
mand output signal.
%/.&21
)XQFWLRQDOLW\
BLKCON is used for blocking of functions in a bay and in an apparatus control pro-
gram. BLKCONL (x=1) contains one blocking function and BLKCONK (x=1, 2 and 3)
contains three blocking functions. The blocking function can be controlled by both
steady and pulse signals. The functionality can be represented by logic as in Figure 89
below.
BLK_x_1
BLK_x_2
BLK_x_3
BLKCMDx
S
DBLCMDx
R
BYPASSx
)LJXUH  7KH IXQFWLRQ RI %/.&21 UHSUHVHQWHG E\ ORJLF
&RQILJXUDWLRQ
*HQHUDO
This part describes type solutions for connection to other application functions. All
functions are described in separate chapters. A standard configuration for a single-
breaker bay with double busbars including five high-voltage apparatusës can be found
in an "Example configuration". Figure 90 shows an overview of a circuit breaker mod-
BLK_OUTx
&
>1
x = 1, 2, or 3
99000327.vsd
&KDSWHU 