ABB REO 517 Applications Manual page 323

Multi-function terminals for railway application
Table of Contents

Advertisement


Disturbance report (DRP)
Analog-signal trigger (over/under function)
0DQXDO WULJJHU
A disturbance report can be manually triggered from the local HMI, a front-connected
PC, or SMS. When the trigger is activated, the manual trigger signal is generated. This
feature is especially useful for testing. Refer to Operators manual for procedure.
%LQDU\ WULJJHU
Any binary signal state (logic one or a logic zero) can be selected to generate a trigger.
The binary signal must remain in a steady state for at least 15 ms to be valid.
When a binary signal is selected to generate a trigger from a logic zero, the selected sig-
nal will not be listed in the indications list of the disturbance report.
$QDORJ WULJJHU
All analog signals are available for trigger purposes, no matter if they are recorded in
the disturbance recorder or not. But the disturbance recorder function must be installed
in the terminal.
5HWULJJHU
Under certain circumstances the fault condition may reoccur during the postfault re-
cording, for instance by automatic reclosing to a still faulty network. In order to capture
the new fault it is possible to allow retriggering during the PostFault recording.
&DOFXODWLRQV
The parameters for the disturbance report function are set via the local HMI or PST (Pa-
rameter Setting Tool). Refer to the Technical reference manual for setting parameters
and path in local HMI.
The settings include:
2SHUDWLRQ
Disturbance Report (On/Off)
5H7ULJ
Re-trigger during post-fault state (On/Off)
6HTXHQFH1R
Sequence number (0-255) (normally not necessary to set)
5HFRUGLQJ7LPHV
Recording times for the Disturbance Report and the event/indication
logging, including pre-fault time, post-fault time, and limit time for the
entire disturbance
&KDSWHU 
0RQLWRULQJ
313

Advertisement

Table of Contents
loading

Table of Contents