ABB REO 517 Applications Manual page 159

Multi-function terminals for railway application
Table of Contents

Advertisement

Line test function (LITE)
When the input signals LITE-TESTON and LITE-TROPEN are activated and the input
signal LITE-TESTOFF is not activated, the output signal LITE-INTEST is activated
while the output signal LITE-NOTEST is not activated. If the input signals LITE-
START and LITE-TBCLOSED are also activated, and the setting Operation=Voltage
check or Operation=Line test has been selected, a 200 ms pulse will be sent on the out-
put LITE-CLOSECB.
When the input signals LITE-TESTOFF and LITE-TROPEN are activated and the in-
put signal LITE-TESTON is not activated, the output signal LITE-NOTEST is activat-
ed and the output signal LITE-INTEST is deactivated. If the input signal LITE-
CLOSECB is activated, the output signals LITE-OPENCB and LITE-STARTAR will
be activated after 200 ms.
LITE-BLOCK
LIT E-T EST ON
LIT E-T ROPEN
LITE-TESTOFF
LIT E-CBCLO SED
ULine
ULTest>
LIT E-T BCLO SED
LITE-START
Operation = Line test
Operation = Voltage test
ULine
ULNormal>
UBusbar
UBNormal
)LJXUH  6LPSOLILHG ORJLF GLDJUDP IRU OLQH WHVWLQJ IXQFWLRQ
&
S
1
R
≥1
≥1
&
t
&
≥1
&
t=100 ms
&
t
t=200 ms
t
&
t=200 ms
t
≥1
&KDSWHU 
9ROWDJH
&
LITE-INTEST
&
LITE-NOTEST
&
LITE-OPENCB
&
LITE-STARTAR
&
LITE-CLOSECB
&
LITE-BLKTB
en02000558.v sd
149