Automatic reclosing function (AR)
$XWRPDWLF FRQILUPDWLRQ RI SURJUDPPHG UHFORVLQJ DWWHPSWV
The auto-recloser can be programmed to continue with reclosing attempts two to four
(if selected) even if the start signals are not received from the protection functions, but
the breaker is still not closed. See figure in Function block diagrams. This is done by
setting the parameter $XWR&RQW = On and the wait time W$XWR:DLW to desired length.
&DOFXODWLRQV
&RQILJXUDWLRQ DQG VHWWLQJ
The signals are configured in the CAP configuration tool.
The parameters for the automatic reclosing function are set via the local HMI or PST
(Parameter Setting Tool). Refer to the Technical reference manual for setting parame-
ters and path in local HMI.
5HFRPPHQGDWLRQV IRU LQSXW VLJQDOV
See figure 77 "Recommendations for I/O-signal connections" on page 179 and the de-
fault configuration for examples.
$567$57
Should be connected to the protection function trip output which shall start the auto-re-
closer. It can also be connected to a binary input for start from an external contact. A
logical OR gate can be used to multiply the number of start sources.
$521 DQG $52))
May be connected to binary inputs for external control.
$5,1+,%,7
Can be connected to binary inputs, to block the AR from a certain protection, such as a
line connected shunt reactor, transfer trip receive or back-up protection or breaker-fail-
ure protection.
$5&%&/26(' DQG $5&%5($'<
Must be connected to binary inputs, for pick-up of the breaker signals. If the external
signals are of Breaker-not-ready type, uncharged etc., an inverter can be configured be-
fore CBREADY.
$56<1&
Is connected to the internal synchro-check function if required. It can also be connected
to a binary input. If neither internal nor external synchronizing or energizing check
(dead line check) is required, it can be connected to a permanent 1 (high), by connection
to FIXD-ON.