Sudden current change function (SCC)
ZnRW-
START
SVC-
START
SCC-START
)LJXUH  ([DPSOH RI WKH WULSSLQJ ORJLF IRU WKH LPSHGDQFH SURWHFWLRQ DQG WKH IXQF
WLRQV 69& DQG 6&&
&DOFXODWLRQV
The parameters for the sudden current change function are set via the local HMI or PST
(Parameter Setting Tool). Refer to the Technical reference manual for setting parame-
ters and path in local HMI.
The setting of the operate value for the sudden change current measuring element di/dt
must be greater than highest expected load current change on the protected line. It is
necessary with an additional margin of at least 10% above the declared inaccuracy of
the current transformer and measuring element.
The setting of the recovery delay t for the sudden change current measuring element
must be greater than the set time delay of the zone which activates the ZnRW-TRIP sig-
nal plus the operate time of the tripping signal.
1RWH
7KH WLPH PXVW EH VKRUWHU WKDQ WKH GHDG WLPH LQWHUYDO LQ FDVH RI DXWRUHFORVLQJ
The current transformer secondary setting current (Is
I
S EC
Is
------------- - Is
=
SEC
I
PRIM
where I
is the secondary rated current of the main CT and I
SEC
ondary rated current of the main CT.
&
>1
en02000512.vsd
) is:
SEC
&KDSWHU 
&XUUHQW
(Equation 47)
is the primary sec-
PRIM
101