&KDSWHU 
Logic function blocks
&RPPRQ IXQFWLRQV
For details about the function see the description of TM Timer.
3XOVH
The pulse function can be used, for example, for pulse extensions or limiting of opera-
tion of outputs. The pulse timer TP (figure 17) has a settable length of a pulse between
0.00 s and 60.00 s in steps of 0.01 s. The input signal for each pulse timer has the des-
ignation TPnn-INPUT, where nn presents the serial number of the logic block. Each
pulse timer has one output, designated by TPnn-OUT. The pulse timer is not retrigga-
ble, that is, it can be restarted first after that the time T has elapsed.
TPnn
INPUT
OUT
T
Time delay 0.00-60.00s
xx00000524.vsd
)LJXUH  )XQFWLRQ EORFN GLDJUDP RI WKH 3XOVH IXQFWLRQ
The function block TQ pulse timer (figure 18) with extended maximum pulse length, is
identical with the TP pulse timer. The difference is the longer pulse length TQnn-T, set-
table between 0.0 and 90000.0 s in steps of 0.1 s.
TQnn
INPUT
OUT
T
Time delay 0.0-90000.0s
xx00000525.vsd
)LJXUH  )XQFWLRQ EORFN GLDJUDP RI WKH 3XOVH/RQJ IXQFWLRQ 74